1.32 Resistors, resistance boxes and potential dividers
.03 DC shunts
with least uncertainties of measurement of
0.1% from 0.1 Ato 5 A
0.015% from 5 A to 20 A
0.02% from 20 A to 120 A
0.09% from 120 A to 400A
1.39 Indicating and recording instruments
.01 D.C. voltmeters
with least uncertainties of measurement of
0.0083% from 100 µV to 100 mV
0.0033% from 0.1 V to 1 V
0.0029% from 1 V to 10 V
0.0044% from 10 V to 100 V
0.0046% from 100 V to 1000 V
.02 A.C. voltmeters
with least uncertainties of measurement of
From 10 mV to 750 V
0.09% from 10 Hz to 20 kHz
0.15% from 20 kHz to 50 kHz
0.48% from 50 kHz to 100 kHz
from 750 V to 1000 V
0.09% from 10 Hz to 20 kHz
0.17% from 20 kHz to 50 kHz
0.68% from 50 kHz to 100 kHz
.03 D.C. ammeters
with least uncertainties of measurement of
0.05% + 50 nA from 100 µAto 1 mA
0.05% +2 µAfrom1 mA to 10 mA
0.05% +5 µA from 10 mA to 100 mA
0.05% +0.2 mA from 100 mA to 1 A
0.10%+6 mA from 1 A to 3 A
0.15%+8 mA from 3 A to 5 A
0.016% from 5 A to 20 A
0.021% from 20 A to 120 A
0.10% from 120 A to 400 A
.04 A.C. ammeters
with least uncertainties of measurement of
0.14%from10 Hz to 5 kHz from10 mAto 3 A
0.21%from10 Hz to 5 kHz from3 Ato 10 A
0.10%from50 Hz to 60 Hz and at 400 Hz from 5 to 20 A
0.11% from 50 Hz to 60 Hz from 20 A to 120 A
.05 Wattmeters
DC power from 1 to 1000V and 0.1 to 400 A (limited to 50kW) with least uncertainties of measurement of 0.14%
Active Power from 1 to 750 V and 0.1 to 120 A (limited to 50kW) at Unity Power-factor from 50 to 60 Hz
with least uncertainties of measurement of 0.22%
3.07 Power supplies and stabilisers
.01 Power supplies
with least uncertainties of measurement of based on 1.39.01, 1.39.02, 1.39.03 and 1.39.04
.03 Power conditioners
with least uncertainties of measurement of based on 1.39.01, 1.39.02, 1.39.03 and 1.39.04
3.11 Power supply equipment and systems
.01 Electric parameters
Measurement of voltage, current, active power up to 400 Hz with least uncertainties of measurement of based on 1.39.01, 1.39.02, 1.39.03 and 1.39.04